SPDT Air Pressure Switch Adjustable 0.05" - 12" W.C.
Cleveland AFS Air Pressure Switch

More about this product
Please Note: To precisely calibrate a Cleveland Controls air switch, a digital manometer is recommended to confirm set point at actual operating temperature.
Details:
- Snap-acting SPDT switch
- Two 1/4" - 18 NPT female fittings
- Enclosure covered switch terminals
- Set point range: 0.05 ± 0.02" - 12.0" W.C.
- Approximate Switching Differential: Progressive, increasing from 0.02 ± 0.01" W.C at minimum set point to approximately 0.8 " W.C at maximum set point.
- Mounting flanges with four 9/32" mounting holes
- Conduit Opening: one ⅞" diameter opening, accept ½" conduit
- Maximum Pressure: ½ psi (0.03 bar).
- Operating Temperature Range: -40 ºF to 180 ºF (-40 ºC to 82 ºC).
- 100,000 cycle minimum lifespan at ½ psi maximum pressure each cycle and at maximum rated electrical load.
-
Product Downloads
-
Manufacturer Info
Cleveland