DPDT Air Pressure Switch Adjustable 4"- 12" W.C. Manual Reset
Cleveland AFS Air Pressure Switch

More about this product
Please Note: To precisely calibrate a Cleveland Controls air switch, a digital manometer is recommended to confirm set point at actual operating temperature.
Details:
- Snap-acting DPDT switch
- Two ferrule and nut compression type connectors will accept .25" OD rigid tubing
- Enclosure covered switch terminals
- Set point range: 0.40 ± 0.06" - 12.0" W.C.
- Standard foot bracket
- Conduit Opening: one ⅞" diameter opening, accept ½" conduit
- Maximum Pressure: ½ psi (0.03 bar).
- Operating Temperature Range: -40 ºF to 180 ºF (-40 ºC to 82 ºC).
- 100,000 cycle minimum lifespan at ½ psi maximum pressure each cycle and at maximum rated electrical load.
-